engine.solvers.sustainability
engine.solvers.sustainability
Sustainability solvers: facility power, run footprints, carbon placement, time shifting, and demand.
Domain implementations behind mlsysim.solvers (the public import path, derived from engine.solvers.__init__); kept per-domain so the logic stays reviewable. Added 2026-10-20.
Every model here works on a rated-power (TDP) basis unless a caller passes a measured power: these are upper-bound planning accounts, not meter readings. The power chain is accelerator power, times the rack’s IT-to-accelerator ratio (hosts, switches, conversion inside the IT boundary), times PUE (facility overhead, applied once at the facility boundary). Carbon is facility energy times a grid carbon intensity.
Classes
| Name | Description |
|---|---|
| CarbonPricedPlacementModel | Placement of one run among regions with and without a carbon price. |
| CascadeEnergyModel | Edge-first cascade: every input runs a small edge model; a fraction |
| DataMovementEnergyModel | Modeled dynamic energy of using one weight: arithmetic against moving it. |
| DemandReboundModel | Fleet energy after a per-unit efficiency change and a volume change: e x v. |
| DevelopmentSweepModel | Final-run equivalents a development sweep consumes: candidates x relative cost. |
| DutyCycledPowerModel | Average power of stages each active a fraction of the time, against a reference always-on power. |
| EmbodiedPaybackModel | Time for a more efficient replacement to repay its manufacturing carbon. |
| FacilityPowerModel | The power chain from accelerators to the facility meter. |
| GridPlacementModel | One facility energy placed on several grids, optionally after an energy cut. |
| PueRetrofitModel | Energy and cost saved by lowering PUE under a fixed IT load over a period. |
| RepeatedWorkEnergyModel | Accelerator energy repeated when a fleet rolls back by each named interval. |
| RunFootprintModel | One training run’s energy, operational carbon, embodied carbon, and water. |
| ServiceLifeExtensionModel | Cut in embodied carbon charged per year when a service life grows: 1 - short / long. |
| ServingCrossoverModel | Calculate serving days needed to match a one-time energy expenditure. |
| TemporalShiftModel | Deadline-constrained carbon-aware time shifting of one flexible run. |
| WaterUseModel | Water consumed for an IT energy at a water usage effectiveness: W = E_IT x WUE. |
CarbonPricedPlacementModel
engine.solvers.sustainability.CarbonPricedPlacementModel()Placement of one run among regions with and without a carbon price.
The run’s duration is the days the fleet needs to spend it_energy at mfu (EconomicsModel’s IT energy per day is region-independent); the PlacementOptimizer then ranks regions by total cost, once with the carbon price and once without.
Methods
| Name | Description |
|---|---|
| solve | Placement of one run among regions with and without a carbon price. |
solve
engine.solvers.sustainability.CarbonPricedPlacementModel.solve(
fleet,
it_energy,
regions,
carbon_price_per_ton,
mfu,
reference_grid,
)Placement of one run among regions with and without a carbon price.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| fleet | object | Fleet supplying accelerator count, power, price, and environment defaults. | required |
| it_energy | Quantity | IT energy in kWh or compatible units; nonnegative. | required |
| regions | List[str] | Nonempty list of registered grid names; unrecognized names are skipped. | required |
| carbon_price_per_ton | float | Nonnegative carbon price in USD per metric ton CO2e. | required |
| mfu | float | Dimensionless model FLOPs utilization in [0, 1]. | required |
| reference_grid | object | Grid profile used to determine the region-independent IT energy per day. | required |
Returns
| Name | Type | Description |
|---|---|---|
| CarbonPricedPlacementResult | Duration in days, chosen regions, and taxed/untaxed objective mappings in USD. |
Notes
Equation: duration_days = IT_energy / modeled_IT_energy_per_day; objective[region] = TCO[region] + carbon_tonnes[region] * carbon_price_per_ton.
Assumptions: EconomicsModel gives region-independent IT energy per day; candidates share fleet and MFU. Excludes: Region-specific runtime changes, data-transfer bills, and deployment eligibility.
References
Derivation: Convert the fixed IT-energy budget to duration, then enumerate EconomicsModel totals with and without the carbon charge.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = CarbonPricedPlacementModel().solve(Systems.Clusters.Research_256, Q_("1 MWh"), ["Quebec"], 100, 0.5, Infrastructure.Grids.Quebec)
>>> result.best_region == "Quebec"
TrueCascadeEnergyModel
engine.solvers.sustainability.CascadeEnergyModel()Edge-first cascade: every input runs a small edge model; a fraction escalation is sent (transmit) to a large cloud model. Mean energy per input E_edge + p (E_tx + E_cloud) against always sending to the cloud.
Methods
| Name | Description |
|---|---|
| solve | Edge-first cascade: every input runs a small edge model; a fraction. |
solve
engine.solvers.sustainability.CascadeEnergyModel.solve(
edge_energy,
transmit_energy,
cloud_energy,
escalation,
)Edge-first cascade: every input runs a small edge model; a fraction.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| edge_energy | Quantity | Energy spent locally on every input, in joules. | required |
| transmit_energy | Quantity | Transmission energy for an escalated input, in joules. | required |
| cloud_energy | Quantity | Cloud processing energy for an escalated input, in joules. | required |
| escalation | float | Fraction of inputs sent to the cloud, in [0, 1]. | required |
Returns
| Name | Type | Description |
|---|---|---|
| CascadeEnergyResult | Escalated, mean, and cloud-only energies in mJ, plus dimensionless relative saving. |
Notes
Equation: cloud_only = transmit_energy + cloud_energy; mean = edge_energy + escalation * cloud_only; saving = 1 - mean / cloud_only.
Assumptions: Every input pays edge cost; a fixed fraction also pays transmission and cloud costs. Excludes: Accuracy changes, queueing, retries, and load-dependent power.
References
Derivation: Use the expectation of a two-branch decision: fixed edge cost plus escalation probability times remote cost.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = CascadeEnergyModel().solve(Q_("1 mJ"), Q_("1 mJ"), Q_("10 mJ"), 0.1)
>>> result.mean_energy < result.cloud_only_energy
TrueDataMovementEnergyModel
engine.solvers.sustainability.DataMovementEnergyModel()Modeled dynamic energy of using one weight: arithmetic against moving it.
A weight of bytes_per_param read once for flops_per_param FLOPs costs bytes x E_byte to move and FLOPs x E_flop to compute. The energy crossover E_byte / E_flop is the arithmetic intensity at which the two match; operand_bytes prices one operand fetch against one FLOP.
Methods
| Name | Description |
|---|---|
| solve | Modeled dynamic energy of using one weight: arithmetic against moving it. |
solve
engine.solvers.sustainability.DataMovementEnergyModel.solve(
energy_per_flop,
energy_per_byte,
flops_per_param,
bytes_per_param,
operand_bytes,
)Modeled dynamic energy of using one weight: arithmetic against moving it.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| energy_per_flop | Quantity | Positive dynamic arithmetic energy in pJ/flop. | required |
| energy_per_byte | Quantity | Positive transfer energy in pJ/byte. | required |
| flops_per_param | float | Positive arithmetic operation count per weight use. | required |
| bytes_per_param | Quantity | Positive bytes transferred for one weight. | required |
| operand_bytes | Quantity | Positive bytes transferred for one operand fetch. | required |
Returns
| Name | Type | Description |
|---|---|---|
| DataMovementEnergyResult | Compute, transfer, and operand energies in pJ; dimensionless energy ratios; arithmetic intensities in FLOP per byte; and a dimensionless balance batch. |
Notes
Equation: compute_energy = flops_per_param * energy_per_flop; movement_energy = bytes_per_param * energy_per_byte; crossover_intensity = energy_per_byte / energy_per_flop.
Assumptions: Each weight is transferred once per modeled use; energy per operation and byte is fixed. Excludes: Caches, static power, communication protocols, and precision- dependent kernel effects.
References
Derivation: Price the operation and byte counts separately; equating their energies gives the energy ridge point E_byte/E_flop.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = DataMovementEnergyModel().solve(Q_("1 pJ/flop"), Q_("10 pJ/byte"), 2, Q_("2 byte"), Q_("2 byte"))
>>> result.movement_energy > result.compute_energy
TrueDemandReboundModel
engine.solvers.sustainability.DemandReboundModel()Fleet energy after a per-unit efficiency change and a volume change: e x v.
Methods
| Name | Description |
|---|---|
| solve | Fleet energy after a per-unit efficiency change and a volume change: e x v. |
solve
engine.solvers.sustainability.DemandReboundModel.solve(
per_unit_factor,
volume_factor,
)Fleet energy after a per-unit efficiency change and a volume change: e x v.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| per_unit_factor | float | Nonnegative new-to-old energy ratio per unit of work. | required |
| volume_factor | float | Nonnegative new-to-old workload volume ratio. | required |
Returns
| Name | Type | Description |
|---|---|---|
| DemandReboundResult | Dimensionless total-energy ratio after both changes. |
Notes
Equation: net_factor = per_unit_factor * volume_factor.
Assumptions: Per-unit energy and total volume factors multiply independently. Excludes: Causal prediction of induced demand and changes in workload mix.
References
Derivation: Total energy is energy per unit times unit count; dividing new by old cancels the baseline units.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = DemandReboundModel().solve(0.5, 2)
>>> result.net_factor == 1
TrueDevelopmentSweepModel
engine.solvers.sustainability.DevelopmentSweepModel()Final-run equivalents a development sweep consumes: candidates x relative cost.
Methods
| Name | Description |
|---|---|
| solve | Final-run equivalents a development sweep consumes: candidates x relative cost. |
solve
engine.solvers.sustainability.DevelopmentSweepModel.solve(
candidates,
relative_cost,
)Final-run equivalents a development sweep consumes: candidates x relative cost.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| candidates | float | Nonnegative number of development candidates. | required |
| relative_cost | float | Nonnegative cost per candidate relative to a final run. | required |
Returns
| Name | Type | Description |
|---|---|---|
| DevelopmentSweepResult | Dimensionless development cost measured in final-run equivalents. |
Notes
Equation: final_run_equivalents = candidates * relative_cost.
Assumptions: Every candidate has the same supplied relative cost. Excludes: Failed runs, shared preprocessing, and variable candidate budgets.
References
Derivation: Sum equal candidate costs after normalizing each by final-run cost.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = DevelopmentSweepModel().solve(4, 0.5)
>>> result.final_run_equivalents == 2
TrueDutyCycledPowerModel
engine.solvers.sustainability.DutyCycledPowerModel()Average power of stages each active a fraction of the time, against a reference always-on power.
Methods
| Name | Description |
|---|---|
| solve | Average power of stages each active a fraction of the time, against a reference always-on power. |
solve
engine.solvers.sustainability.DutyCycledPowerModel.solve(
powers,
duty_cycles,
reference_power,
)Average power of stages each active a fraction of the time, against a reference always-on power.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| powers | Dict[str, Quantity] | Nonempty mapping of stage names to nonnegative power quantities. | required |
| duty_cycles | Dict[str, float] | Stage-name mapping to active fractions in [0, 1]; must cover powers. | required |
| reference_power | Quantity | Positive always-on comparison power in watts. | required |
Returns
| Name | Type | Description |
|---|---|---|
| DutyCycledPowerResult | Stage contributions and average power in microwatts, and reference-to- average power ratio. |
Notes
Equation: average_power = sum(stage_power * stage_duty); reduction = reference_power / average_power.
Assumptions: Stage powers are additive; duty fractions describe the same observation window. Excludes: Sleep leakage, switching energy, and correlated peak-power constraints.
References
Derivation: Time-averaging each rectangular active-power contribution gives power times duty fraction; add the contributions.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = DutyCycledPowerModel().solve({"stage": Q_("10 W")}, {"stage": 0.5}, Q_("10 W"))
>>> result.average_power == Q_("5 W")
TrueEmbodiedPaybackModel
engine.solvers.sustainability.EmbodiedPaybackModel()Time for a more efficient replacement to repay its manufacturing carbon.
The replacement does the old device’s work with saved_fraction less energy, running continuously at the old device’s power; the carbon it avoids per day is the saved energy times the grid intensity, and payback is the embodied carbon divided by that daily saving.
Methods
| Name | Description |
|---|---|
| solve | Time for a more efficient replacement to repay its manufacturing carbon. |
solve
engine.solvers.sustainability.EmbodiedPaybackModel.solve(
embodied,
device_power,
saved_fraction,
intensities,
)Time for a more efficient replacement to repay its manufacturing carbon.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| embodied | Quantity | Replacement manufacturing carbon in kg CO2e; nonnegative. | required |
| device_power | Quantity | Power per accelerator in watts; nonnegative rated or supplied measured power. | required |
| saved_fraction | float | Fraction of baseline power avoided, in (0, 1]. | required |
| intensities | Dict[str, Quantity] | Nonempty mapping of grid names to positive carbon intensities in g/kWh. | required |
Returns
| Name | Type | Description |
|---|---|---|
| EmbodiedPaybackResult | Saved power in kW, daily energy in kWh, daily avoided carbon in kg, and per- grid payback times in days. |
Notes
Equation: saved_power = device_power * saved_fraction; avoided_carbon_per_day = saved_power * one_day * intensity; payback = embodied / avoided_carbon_per_day.
Assumptions: Replacement provides equal useful work continuously; power saving and positive grid intensities stay fixed. Excludes: Idle periods, changing demand, old-device disposal, and discounting future emissions.
References
Derivation: Divide the one-time manufacturing carbon by avoided carbon per day to obtain a carbon-balance time.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = EmbodiedPaybackModel().solve(Q_("1 kg"), Q_("1 kW"), 0.5, {"site": Q_("100 g/kWh")})
>>> result.payback["site"] > Q_("0 day")
TrueFacilityPowerModel
engine.solvers.sustainability.FacilityPowerModel()The power chain from accelerators to the facility meter.
Accelerator power is devices x device_power; the IT load multiplies it by the rack’s IT-to-accelerator ratio (hosts, switches, network adapters, and conversion losses inside the IT boundary); the facility draws the IT load times PUE. The facility figure is what the grid connection must supply at every instant.
Methods
| Name | Description |
|---|---|
| solve | The power chain from accelerators to the facility meter. |
solve
engine.solvers.sustainability.FacilityPowerModel.solve(
devices,
device_power,
it_ratio,
pue,
)The power chain from accelerators to the facility meter.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| devices | float | Accelerator count, positive and dimensionless. | required |
| device_power | Quantity | Power per accelerator in watts; nonnegative rated or supplied measured power. | required |
| it_ratio | float | Dimensionless IT-to-accelerator power ratio, at least one for this boundary. | required |
| pue | float | Dimensionless facility-to-IT energy ratio, at least one. | required |
Returns
| Name | Type | Description |
|---|---|---|
| FacilityPowerResult | Accelerator, IT, facility, support, and facility-overhead powers in MW. |
Notes
Equation: P_acc = devices * device_power; P_IT = P_acc * it_ratio; P_facility = P_IT * PUE.
Assumptions: All devices draw the same supplied power; ratios describe nested boundaries. Excludes: Transient peaks, redundancy margins, and capacity admission.
References
Derivation: Apply each boundary ratio once; subtract accelerator from IT and IT from facility to isolate overhead.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = FacilityPowerModel().solve(2, Q_("100 W"), 1.2, 1.1)
>>> result.facility_power > result.it_power
TrueGridPlacementModel
engine.solvers.sustainability.GridPlacementModel()One facility energy placed on several grids, optionally after an energy cut.
Emissions are E x CI per grid; energy_cut is a fractional energy reduction applied before the grid factor (an algorithmic saving), so a placement and an efficiency gain can be compared at one energy.
Methods
| Name | Description |
|---|---|
| solve | One facility energy placed on several grids, optionally after an energy cut. |
solve
engine.solvers.sustainability.GridPlacementModel.solve(
energy,
intensities,
energy_cut=0.0,
)One facility energy placed on several grids, optionally after an energy cut.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| energy | Quantity | Facility energy in kWh; nonnegative. | required |
| intensities | Dict[str, Quantity] | Nonempty mapping of grid names to positive carbon intensities in g/kWh. | required |
| energy_cut | float | Fractional energy reduction in [0, 1]; default zero. | 0.0 |
Returns
| Name | Type | Description |
|---|---|---|
| GridPlacementResult | Emissions before and after the cut in metric tons, lowest/highest intensity grid names, and their dimensionless intensity ratio. |
Notes
Equation: emissions[grid] = energy * intensity[grid]; reduced_emissions = emissions * (1 - energy_cut).
Assumptions: All regions serve identical energy demand and all intensities are positive. Excludes: Regional latency, electricity cost, marginal dispatch, and placement feasibility.
References
Derivation: At fixed energy, carbon ordering equals intensity ordering; scale both by the same fractional energy saving.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = GridPlacementModel().solve(Q_("1 kWh"), {"low": Q_("10 g/kWh"), "high": Q_("100 g/kWh")})
>>> result.lowest == "low"
TruePueRetrofitModel
engine.solvers.sustainability.PueRetrofitModel()Energy and cost saved by lowering PUE under a fixed IT load over a period.
Methods
| Name | Description |
|---|---|
| solve | Energy and cost saved by lowering PUE under a fixed IT load over a period. |
solve
engine.solvers.sustainability.PueRetrofitModel.solve(
it_power,
pue_before,
pue_after,
period,
electricity_price,
)Energy and cost saved by lowering PUE under a fixed IT load over a period.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| it_power | Quantity | Constant IT load in watts; nonnegative. | required |
| pue_before | float | Initial dimensionless PUE, at least one. | required |
| pue_after | float | Replacement dimensionless PUE, at least one. | required |
| period | Quantity | Duration in hours or compatible time units; nonnegative. | required |
| electricity_price | Quantity | Energy price in USD/kWh; nonnegative. | required |
Returns
| Name | Type | Description |
|---|---|---|
| PueRetrofitResult | Before/after facility powers and saved power in MW, saved energy in MWh, and saved electricity cost in USD. |
Notes
Equation: saved_power = IT_power * (PUE_before - PUE_after); saved_energy = saved_power * period; saved_cost = saved_energy * price.
Assumptions: IT load and electricity price stay fixed across both PUE cases. Excludes: Retrofit capital cost, downtime, and changes in IT demand.
References
Derivation: Subtract the facility-power products before integrating over the period; price only the energy difference.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = PueRetrofitModel().solve(Q_("1 kW"), 1.4, 1.2, Q_("1 day"), Q_("0.1 USD/kWh"))
>>> result.saved_energy > Q_("0 kWh")
TrueRepeatedWorkEnergyModel
engine.solvers.sustainability.RepeatedWorkEnergyModel()Accelerator energy repeated when a fleet rolls back by each named interval.
Methods
| Name | Description |
|---|---|
| solve | Accelerator energy repeated when a fleet rolls back by each named interval. |
solve
engine.solvers.sustainability.RepeatedWorkEnergyModel.solve(
devices,
device_power,
rollbacks,
)Accelerator energy repeated when a fleet rolls back by each named interval.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| devices | float | Accelerator count, positive and dimensionless. | required |
| device_power | Quantity | Power per accelerator in watts; nonnegative rated or supplied measured power. | required |
| rollbacks | Dict[str, Quantity] | Named nonnegative rollback intervals in time units. | required |
Returns
| Name | Type | Description |
|---|---|---|
| RepeatedWorkEnergyResult | Named rollback energy expenditures in MWh. |
Notes
Equation: energy[interval] = devices * device_power * rollback_time[interval].
Assumptions: All devices repeat work at constant supplied power for each interval. Excludes: Recovery I/O, idle power, and facility overhead.
References
Derivation: Integrate fleet accelerator power over each repeated-work interval.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = RepeatedWorkEnergyModel().solve(2, Q_("100 W"), {"short": Q_("1 hour"), "long": Q_("2 hour")})
>>> result.energy["long"] == 2 * result.energy["short"]
TrueRunFootprintModel
engine.solvers.sustainability.RunFootprintModel()One training run’s energy, operational carbon, embodied carbon, and water.
Energy follows the power chain over the run’s device-hours: accelerator energy device_hours x device_power, IT energy times the rack ratio, facility energy times PUE. Operational carbon applies each named grid’s intensity to facility energy. Embodied carbon is devices x embodied_per_device at manufacture; the run is charged its time share, device_hours x embodied_per_device / service_life. Water applies each WUE to IT energy (WUE’s denominator is IT energy).
Methods
| Name | Description |
|---|---|
| solve | One training run’s energy, operational carbon, embodied carbon, and water. |
solve
engine.solvers.sustainability.RunFootprintModel.solve(
device_hours,
devices,
device_power,
it_ratio,
pue,
intensities,
embodied_per_device,
service_life,
wue=None,
)One training run’s energy, operational carbon, embodied carbon, and water.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| device_hours | Quantity | Aggregate accelerator operating time in hours; count is dimensionless. | required |
| devices | float | Accelerator count, positive and dimensionless. | required |
| device_power | Quantity | Power per accelerator in watts; nonnegative rated or supplied measured power. | required |
| it_ratio | float | Dimensionless IT-to-accelerator power ratio, at least one for this boundary. | required |
| pue | float | Dimensionless facility-to-IT energy ratio, at least one. | required |
| intensities | Dict[str, Quantity] | Nonempty mapping of grid names to positive carbon intensities in g/kWh. | required |
| embodied_per_device | Quantity | Manufacturing carbon per accelerator in kg CO2e; nonnegative. | required |
| service_life | Quantity | Positive service lifetime in hours or compatible time units. | required |
| wue | Optional[Dict[str, Quantity]] | Named water-use factors in liters per kWh of IT energy; nonnegative. | None |
Returns
| Name | Type | Description |
|---|---|---|
| RunFootprintResult | Power breakdown, duration in hours, energy in MWh, operational and embodied carbon in metric tons, embodied fractions, and optional water in liters. |
Notes
Equation: E_acc = device_hours * device_power; E_IT = E_acc * it_ratio; E_facility = E_IT * PUE. Allocated embodied carbon = device_hours * embodied_per_device / service_life.
Assumptions: Device-hours aggregate equal-power accelerators; embodied carbon is allocated uniformly over the supplied service life. Excludes: Manufacturing timing, retirement credits, and variation of grid intensity within the run.
References
Derivation: Integrate device power over aggregate hours, apply the two overhead ratios, and charge manufacturing carbon in proportion to consumed service hours.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = RunFootprintModel().solve(Q_("2 hour"), 2, Q_("100 W"), 1.2, 1.1, {"site": Q_("100 g/kWh")}, Q_("1 kg"), Q_("1 year"))
>>> result.facility_energy > result.it_energy
TrueServiceLifeExtensionModel
engine.solvers.sustainability.ServiceLifeExtensionModel()Cut in embodied carbon charged per year when a service life grows: 1 - short / long.
Methods
| Name | Description |
|---|---|
| solve | Cut in embodied carbon charged per year when a service life grows: 1 - short / long. |
solve
engine.solvers.sustainability.ServiceLifeExtensionModel.solve(
short_life,
long_life,
)Cut in embodied carbon charged per year when a service life grows: 1 - short / long.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| short_life | Quantity | Positive original service life in time units. | required |
| long_life | Quantity | Positive extended service life in compatible time units. | required |
Returns
| Name | Type | Description |
|---|---|---|
| ServiceLifeExtensionResult | Dimensionless reduction in annual embodied-carbon allocation. |
Notes
Equation: annual_charge_reduction = 1 - short_life / long_life.
Assumptions: Identical embodied carbon is spread uniformly over either positive lifetime. Excludes: Replacement operating energy and changes in useful work.
References
Derivation: Annual charges are C/short and C/long; their relative reduction cancels C and equals 1-short/long.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = ServiceLifeExtensionModel().solve(Q_("1 year"), Q_("2 year"))
>>> result.annual_charge_reduction > 0
TrueServingCrossoverModel
engine.solvers.sustainability.ServingCrossoverModel()Calculate serving days needed to match a one-time energy expenditure.
Methods
| Name | Description |
|---|---|
| solve | Calculate serving days needed to match a one-time energy expenditure. |
solve
engine.solvers.sustainability.ServingCrossoverModel.solve(
one_time_energy,
requests_per_day,
energy_per_request,
)Calculate serving days needed to match a one-time energy expenditure.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| one_time_energy | Quantity | One-time energy expenditure in joules or compatible units. | required |
| requests_per_day | float | Positive request count per calendar day, supplied as a scalar. | required |
| energy_per_request | Quantity | Positive energy per request in joules; request count is dimensionless. | required |
Returns
| Name | Type | Description |
|---|---|---|
| ServingCrossoverResult | Daily serving energy in MWh and dimensionless elapsed day count at crossover. |
Notes
Equation: daily_energy = requests_per_day * energy_per_request; crossover_days = one_time_energy / daily_energy.
Assumptions: Positive constant daily request volume and per-request energy. Excludes: Load growth, idle infrastructure, and latency constraints.
References
Derivation: Divide one-time energy by daily serving energy; each quotient unit denotes one day of demand.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = ServingCrossoverModel().solve(Q_("1 kWh"), 100, Q_("1 J"))
>>> result.crossover_days > 0
TrueTemporalShiftModel
engine.solvers.sustainability.TemporalShiftModel()Deadline-constrained carbon-aware time shifting of one flexible run.
Picks the start time with the lowest total emissions among starts that finish by the deadline and have capacity. Waiting is charged the extra energy it causes, so a later start wins only if it avoids more carbon than the wait adds.
Methods
| Name | Description |
|---|---|
| solve | Best deadline-feasible start of one flexible run on a time-varying grid signal. |
solve
engine.solvers.sustainability.TemporalShiftModel.solve(
intensities,
power,
duration,
slack,
step=None,
deferral_energy=None,
standby_power=None,
capacity_available=None,
)Best deadline-feasible start of one flexible run on a time-varying grid signal.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| intensities | List[Quantity] | Carbon intensity per step, in g/kWh or compatible units, starting at the run’s release; finite and nonnegative; must cover duration + slack. Average or marginal intensity is the caller’s choice. |
required |
| power | Quantity | Facility power while the run executes (IT power times PUE), in kW or compatible units; finite and nonnegative. | required |
| duration | Quantity | Run duration; a positive whole number of steps. | required |
| slack | Quantity | The run must finish by release + duration + slack; a nonnegative whole number of steps. Zero forces an immediate start. | required |
| step | Quantity | Length of one signal step; default one hour. | None |
| deferral_energy | Quantity | One-time extra energy caused by deferring, such as restaging input data, in kWh or compatible units; finite and nonnegative; default zero. | None |
| standby_power | Quantity | Extra power drawn while waiting, such as reserved capacity kept powered, in kW or compatible units; finite and nonnegative; default zero. Use zero if the hardware draws that power either way. | None |
| capacity_available | List[bool] | Per-step bool: True if capacity is free. A start is feasible only if every step it occupies is free. Non-bool values are rejected. Default: all free. | None |
Returns
| Name | Type | Description |
|---|---|---|
| TemporalShiftResult | Chosen start and completion time; start-now, run, overhead, and net emissions in kg CO2e; net saving and saving fraction (None if start-now emits nothing); net emissions per candidate start (None if infeasible); and the shortest wait that saves carbon (None if none does). |
Notes
Equation: with n run steps, step energy E = power * step, and candidate wait k in {0, …, slack/step}, run(k) = sum over t from k to k+n-1 of E * CI[t]; overhead(0) = 0 and, for k > 0, overhead(k) = deferral_energy * CI[0] + sum over t from 0 to k-1 of standby_power * step * CI[t]; net(k) = run(k) + overhead(k). Among starts with capacity in steps k to k+n-1, the chosen wait minimizes net(k), taking the earliest wait on ties, and net_saving = net(0) - min net(k). If start-now has no capacity, net(0) is hypothetical (immediate_feasible is False) and net_saving can be negative.
Assumptions: The run is non-preemptive and contiguous; power is constant; intensity is uniform within each step; deferral energy is drawn at release. Excludes: Pausing or migrating a started run, partial capacity, forecast error, runtime changes from moving the run, failures, and penalties other than the hard deadline.
References
Derivation: Emissions are energy times intensity summed per step; checking every feasible start gives the exact minimum. Related work: Radovanovic et al., Carbon-Aware Computing for Datacenters, https://arxiv.org/abs/2106.11750.
Examples
>>> from mlsysim import Q_
>>> signal = [Q_(500, "g/kWh"), Q_(500, "g/kWh"), Q_(100, "g/kWh")]
>>> result = TemporalShiftModel().solve(signal, Q_("10 kW"), Q_("1 hour"), Q_("2 hour"))
>>> result.best_start.m_as("hour"), result.net_saving.m_as("kg")
(2.0, 4.0)WaterUseModel
engine.solvers.sustainability.WaterUseModel()Water consumed for an IT energy at a water usage effectiveness: W = E_IT x WUE.
Methods
| Name | Description |
|---|---|
| solve | Water consumed for an IT energy at a water usage effectiveness: W = E_IT x WUE. |
solve
engine.solvers.sustainability.WaterUseModel.solve(it_energy, wue)Water consumed for an IT energy at a water usage effectiveness: W = E_IT x WUE.
Parameters
| Name | Type | Description | Default |
|---|---|---|---|
| it_energy | Quantity | IT energy in kWh or compatible units; nonnegative. | required |
| wue | Dict[str, Quantity] | Named water-use factors in liters per kWh of IT energy; nonnegative. | required |
Returns
| Name | Type | Description |
|---|---|---|
| WaterUseResult | Mapping of site names to water quantities in liters. |
Notes
Equation: water[site] = IT_energy * WUE[site], converted to liters.
Assumptions: Every WUE uses IT energy as its denominator and remains constant. Excludes: Supply-chain water and facility-energy WUE conventions.
References
Derivation: Multiply liters per IT kWh by IT kWh; the energy unit cancels.
Examples
>>> from mlsysim import Q_, Systems, Infrastructure
>>> result = WaterUseModel().solve(Q_("1 kWh"), {"site": Q_("1 liter/kWh")})
>>> result.water["site"] == Q_("1 liter")
True