Facility solvers: power transients, coolant flow, and outage cost.

Domain implementations behind mlsysim.solvers (the public import path, derived from engine.solvers.__init__); kept per-domain so the logic stays reviewable.

Classes

Name Description
CoolantFlowModel Coolant flow that carries a heat load at a stated temperature rise.
OutageCostModel Idle cost of a failure domain going down during a synchronous job.
PowerTransientModel One accelerator’s load step and the ramp a synchronized cluster produces.

CoolantFlowModel

engine.solvers.facility.CoolantFlowModel()

Coolant flow that carries a heat load at a stated temperature rise.

m_dot = Q / (c_p dT), then volume flow from the coolant’s density. Water’s specific heat is about four times air’s and its density about 830 times, so it carries the same heat in thousands of times less volume.

Methods

Name Description
solve Calculate coolant mass and volume flow for a steady heat load.
solve
engine.solvers.facility.CoolantFlowModel.solve(
    heat_load,
    temperature_rise,
    coolant='air',
)

Calculate coolant mass and volume flow for a steady heat load.

Parameters
Name Type Description Default
heat_load Quantity Nonnegative heat delivered to the coolant in W. required
temperature_rise Quantity Positive inlet-to-outlet temperature difference in K. required
coolant str Either “air” or “water”; default “air” selects its registered density and specific heat. 'air'
Returns
Name Type Description
CoolantFlowResult Required mass flow in kg/s and volume flow in L/s.
See Also

mlsysim.physics.thermal.calc_coolant_mass_flow : Apply the sensible-heat energy balance.

Notes

Equation: mass_flow = heat_load / (specific_heat * temperature_rise); volume_flow = mass_flow / density.

Assumptions: Steady sensible heat transport and constant coolant properties from physics.constants.

Excludes: Pump or fan power, latent heat, pressure losses, and heat-exchanger effectiveness.

References

Derivation: The steady energy balance Q_dot = m_dot c_p delta_T sets mass flow; dividing by density converts mass flow to volume flow.

Examples
>>> from mlsysim import Q_
>>> a = CoolantFlowModel().solve(Q_(1, "kW"), Q_(10, "K"), "water")
>>> b = CoolantFlowModel().solve(Q_(2, "kW"), Q_(10, "K"), "water")
>>> b.mass_flow == 2 * a.mass_flow
True

OutageCostModel

engine.solvers.facility.OutageCostModel()

Idle cost of a failure domain going down during a synchronous job.

The direct cost counts only the devices in the failed domain. A synchronous job that cannot continue idles every device, and rolling back to the last checkpoint adds the lost work to the repair window.

Methods

Name Description
solve Price repair downtime for a failed domain and its synchronous job.
solve
engine.solvers.facility.OutageCostModel.solve(
    failed_devices,
    job_devices,
    repair_time,
    device_hour_rate,
    rollback_times=None,
)

Price repair downtime for a failed domain and its synchronous job.

Parameters
Name Type Description Default
failed_devices int Nonnegative number of failed devices, no greater than job_devices. required
job_devices int Nonnegative number of devices reserved by the job. required
repair_time Quantity Nonnegative repair duration in hours or compatible time units. required
device_hour_rate Quantity Nonnegative rental or opportunity-cost rate in USD/hour per device. required
rollback_times dict of str to Quantity Named nonnegative lost-work durations added to repair time; None omits rollback scenarios. None
Returns
Name Type Description
OutageCostResult Direct failed-device cost, whole-job idle cost, and each rollback-adjusted job cost, as USD scalars.
Notes

Equation: direct_cost = failed_devices * rate * repair_hours; job_cost = job_devices rate repair_hours; rollback_cost[k] = job_devices * rate * (repair_hours + rollback_hours[k]).

Assumptions: The complete synchronous job is idle during repair, and every reserved device has the same hourly cost.

Excludes: Redundant operation, partial progress, revenue loss, and replacement equipment cost.

References

Derivation: Device-hours equal the number of reserved devices times unavailable hours. Multiplication by the hourly rate gives each cost.

Examples
>>> from mlsysim import Q_
>>> r = OutageCostModel().solve(1, 4, Q_(2, "hour"), Q_(3, "USD/hour"))
>>> r.job_cost == 4 * r.direct_cost
True

PowerTransientModel

engine.solvers.facility.PowerTransientModel()

One accelerator’s load step and the ramp a synchronized cluster produces.

When a collective barrier releases every device from communication into dense arithmetic, each one steps from its communication-phase power toward its design power at once. On one device’s core rail the step is a current change dP / V, and the board loop’s inductance turns a fast edge into a voltage droop L dI/dt. Across the cluster the same step, aligned by the barrier, is a power ramp the facility supplies must follow.

Methods

Name Description
solve Calculate device voltage droop and a synchronized fleet power ramp.
solve
engine.solvers.facility.PowerTransientModel.solve(
    high_power,
    low_power,
    rail_voltage,
    loop_inductance,
    rise_times,
    n_devices,
    ramp_window,
)

Calculate device voltage droop and a synchronized fleet power ramp.

Parameters
Name Type Description Default
high_power Quantity Power after the step in W; at least low_power. required
low_power Quantity Power before the step in W; nonnegative. required
rail_voltage Quantity Positive core supply voltage in V. required
loop_inductance Quantity Nonnegative supply-loop inductance in H. required
rise_times dict of str to Quantity Named positive current-rise times in seconds. required
n_devices int Nonnegative number of synchronized devices. required
ramp_window Quantity Positive facility ramp duration in seconds. required
Returns
Name Type Description
PowerTransientResult Device step in W and A, droop in mV and voltage fractions, fleet step in kW, and ramp in GW/s.
See Also

mlsysim.physics.power.calc_rail_current_step : Compute current change from a power step. mlsysim.physics.power.calc_inductive_droop : Compute ideal inductive voltage droop.

Notes

Equation: dP = high_power - low_power; dI = dP / V; droop = L dI / dt; fleet ramp = n_devices dP / ramp_window.

Assumptions: All devices share one power step and change state together. Each rise time is a separate scenario.

Excludes: Regulator feedback, capacitance, parasitic resistance, and facility supply dynamics. A droop estimate is not a board safety assessment.

References

Derivation: Power P = VI gives the current change at fixed rail voltage; the ideal inductor relation V = L dI/dt gives droop magnitude. Summing identical load steps gives the fleet ramp.

Examples
>>> from mlsysim import Q_
>>> r = PowerTransientModel().solve(Q_(200, "W"), Q_(100, "W"),
...     Q_(1, "V"), Q_(1, "nH"), {"edge": Q_(1, "us")}, 2, Q_(1, "s"))
>>> r.current_step == Q_(100, "A")
True
Back to top